DI water cooling system

Short Description:

Cooling water shall be free from impurities. DOT NOT use well water or river water .To prevent the scale formation, ensure good cooling result, and greatly reduce the failure rate,Soften Water or Distilled Water are strongly recommended as cooling water for induction equipment.

 


Product Detail

Product Tags

DI water cooling system

Cooling water shall be free from impurities. DOT NOT use well water or river water .To prevent the scale formation, ensure good cooling result, and greatly reduce the failure rate,Soften Water or Distilled Water are strongly recommended as cooling water for induction equipment.

PH: 7-8.5

Suspended solids10mg/L

Hardness60mg/L

Conductivity500μA/cm3

Chloride ionAverage60mg/L

Sulfate ion100mg/L

Iron2mg/L

Solubilitysio26mg/L

Dissolved solid300mg/L

DI water cooling system

Cooling

Cooling Tower for DI water cooling system Prepared by customers

Capacity of water tank

Water flow of pump

 Power output of Pump

Lift of pump

Water flow of cooling tower

BKL-250-4.0

Power unit & Heater

15m3/h

4KW

22m

10m3/h

≥5 m3

BKL-250-7.5

Power unit & Heater

25m3/h

4KW

22m

16m3/h

≥10 m3

Feature

  • The use of DI water ensures non-scaling and non-clog in water pipe.
  • Stainless steel DI water tank and connector avoid rusting
  • Small space required, easy to move
  • Low energy loss, operation is simple and reliable.

Specification

Model

BKL-250-4.0

BKL-400-7.5

Cooling capacity

51600Kcal/h

155000 Kcal/h

Water flow

9-18 m3  /h

20-42 m3  /h

Power of water pump

4.0KW

7.5KW

Water capacity of tank

250L

400L

Outside diameter of outlet cooling water

DN40(Quick coupler)

DN65(Flange)

Dimension

1300× 870× 930 (mm)

1550× 1000× 1050 (mm)

Noise

≤70 dB(A)

≤70 dB(A)

Ambient temperature

840℃

840℃

Installation (For reference only)

Model

DI water cooling system

Cooling

Cooling Tower for DI water cooling system Prepared by customers

Capacity of water tank

Water flow of pump

 Power output of Pump

Lift of pump

Water flow of cooling tower

MFP-100D2

BKL-250-4.0

Power unit & Heater

15m3/h

4KW

≥22m

10m3/h

≥5 m3

MFP-160D2

BKL-250-7.5

Power unit & Heater

25m3/h

4KW

≥22m

≥16m3/h

≥10 m3

MFP-250D2

BKL-250-4.0

Power unit

30m3/h

5.5KW

≥22m

≥25m3/h

≥15 m3

BKL-400-7.5

Heater

MFP-350D2

BKL-400-4.0

Power unit

40m3/h

5.5KW

≥22m

≥32m3/h

≥15 m3

BKL-400-7.5

Heater

MFP-500D2

BKL-250-4.0

Power unit

55m3/h

7.5KW

≥22m

≥45m3/h

≥20 m3

BKL-400-7.5

Heater

MFP-600D2

BKL-250-4.0

Power unit

65 m3/h

9.2KW & 11KW

≥22m

55m3/h

≥25 m3

BKL-400-7.5

Heater

MFP-750D2

BKL-250-4.0

Power unit

80m3/h

9.2KW & 11KW

≥22m

70m3/h

≥30 m3

BKL-400-7.5

Heater


  • Previous:
  • Next:

  • Write your message here and send it to us
    -->